Electrical system – JLG 4017RS Service Manual User Manual
Page 190
Electrical System
9-38
3614RS, 4017RS
CABIN JOYSTICK –
RIGHT ROLLER FAULT
2351
Continuously
Right Roller shall be prevented
(Auxiliary Hydraulics)
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf040:E2, 0Xf041:E2,
or 0Xf042:E2
Cabin joystick transmits Error (1:0)
for the Auxiliary Roller Neutral,
Backward, or Forward position
Cabin joystick transmits 1022 as the
Auxiliary Roller position
Machine Setup’s AUXILIARY
FUNCTION SELECT is set to YES, then
log a fault.
Power cycled
CABIN JOYSTICK –
STABILIZER BUTTON
FAULT
2352
Continuously
Button 1 shall be prevented –
Stabilizers
Cabin joystick transmits Error (1:0)
for the Trigger switch
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf061:FF
Power cycled
CABIN JOYSTICK –
NEUTRALIZER
BUTTON FAULT
2329
Continuously
Button 6 shall be prevented –
NEUTRALIZER
Cabin joystick transmits Error (1:0)
for the Neutralizer switch
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf066:FF
Power cycled
CABIN JOYSTICK –
FNR SWITCH FAULT
23115
Continuously
Direction Selection shall be Neutral
Flash both Direction and Gear at
1.25Hz
Cabin joystick transmits a DM1
(SPN:FMI) with 0Xf050:E2, 0Xf051:E2,
or 0Xf052:E2
Cabin joystick transmits Error (1:0)
for the Forward, Neutral, or Reverse
switches
Cabin joystick transmits Switch
Closed (0:1) for more than one
position (Forward, Neutral, Reverse)
for 500Ms
Machine Setup’s TRANS SELECT is
set to JOYSTICK, then log a fault.
Power cycled
OPERATING MODE
INTERLOCK –
OPERATOR PRESENCE
23120
Continuously
–
Machine Setup’s OPERATOR
PRESENCE is YES; and operator is not
present (refer to Operator Presence
functionality)
Operator is
present