Electrical system – JLG 4017RS Service Manual User Manual

Page 194

Advertising
background image

Electrical System

9-42

3614RS, 4017RS

RIGHT STABILIZER UP

VALVE – SHORT TO

BATTERY

33232

Continuously

Stabilizers are prevented

Frame Level is prevented

Short to battery is detected on UGM

J2-3

Power cycled

RIGHT STABILIZER UP

VALVE – SHORT TO

GROUND

33233

5000Ms

Stabilizers are prevented

Short to ground is detected on UGM

J2-3

Power cycled

FRAME LEVEL LEFT

VALVE – OPEN

CIRCUIT

33234

5000Ms

Frame Level Left is prevented

Open circuit is detected on UGM J2-

7

Power cycled

FRAME LEVEL LEFT

VALVE – SHORT TO

BATTERY

33235

Continuously

Stabilizers are prevented

Frame Level is prevented

Short to battery is detected on UGM

J2-7

Power cycled

FRAME LEVEL LEFT

VALVE – SHORT TO

GROUND

33236

5000Ms

Frame Level Left is prevented

Short to ground is detected on UGM

J2-7

Power cycled

FRAME LEVEL RIGHT

VALVE – OPEN

CIRCUIT

33237

5000Ms

Frame Level Right is prevented

Open circuit is detected on UGM J2-

5

Power cycled

FRAME LEVEL RIGHT

VALVE – SHORT TO

BATTERY

33238

Continuously

Stabilizers are prevented

Frame Level is prevented

Short to battery is detected on UGM

J2-5

Power cycled

FRAME LEVEL RIGHT

VALVE – SHORT TO

GROUND

33239

5000Ms

Frame Level Right is prevented

Short to ground is detected on UGM

J2-5

Power cycled

TRANSMISSION

REVERSE COIL – OPEN

CIRCUIT

33246

Continuously

Deactivate output J2-32

Transmission Reverse Coil.

Flash the “Gear Selection” and the

“Drive Direction” symbols on the

LCD of the cabin’s display at 1.25Hz.

Direction Selection shall be Neutral

when Calibration’s TRANS SERVICE is

NO

Open circuit is detected on UGM J2-

32

Power cycled

TRANSMISSION

REVERSE COIL –

SHORT TO BATTERY

33247

Continuously

Deactivate output J2-32

Transmission Reverse Coil.

Flash the “Gear Selection” and the

“Drive Direction” symbols on the

LCD of the cabin’s display at 1.25Hz.

Direction Selection shall be Neutral

when Calibration’s TRANS SERVICE is

NO

Short to battery is detected on UGM

J2-32

Power cycled

TRANSMISSION

REVERSE COIL –

SHORT TO GROUND

33248

Continuously

Deactivate output J2-32

Transmission Reverse Coil.

Flash the “Gear Selection” and the

“Drive Direction” symbols on the

LCD of the cabin’s display at 1.25Hz.

Direction Selection shall be Neutral

when Calibration’s TRANS SERVICE is

NO

Short to ground is detected on UGM

J2-32

Power cycled