High limit input parameters – Despatch Protocol 3 Modbus Communications User Manual

Page 14

Advertising
background image

A

BOUT

T

HIS

M

ANUAL

Modbus Programming Manual

14

Version 2

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Filter time
constant

Process Input
Process Variable

1031

0x0407

R

Process Input
Sensor Break
Flag

1032

0x0408

R

0 = Inactive
1 = Active

Process Input
Under Range
Flag

1033

0x0409

R

0 = Inactive
1 = Active

Process Input
Over Range Flag

1034

0x040A

R

0 = Inactive
1 = Active

Process Input
CJC Enable

1035

0x040B

R/W

0 = Enable
1 = Disabled

Process Input
User Calibration
Type

1085

0x043D

R/W

0 = No User Calibration
1 = Single Point Calibration
2 = Two Point Calibration

Process Input
Low Temperature
Calibration Point

1086

0x043E

R/W

Process Input
Low Calibration
Offset

1087

0x043F

R/W

Process Input
High
Temperature
Calibration Point

1088

0x0440

R/W

Process Input
High Calibration
Offset

1089

0x0441

R/W

2.1.2. High Limit Input Parameters

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

High Limit Input
Range

9000

0x2328

R/W

Value Range
0

B TC

2

C TC

4

D TC

6

J TC

10

K TC

14

L TC

18

N TC

20

R TC

Advertising