2.8. Mode Controls

2.8.1. General Mode Control

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Mode Selection

8285

0x205D

R/W

0 = Do Nothing
1 = Manual Mode
2 = Timer Mode
3 = Profile Mode
4 = Mode Selection

Digital input
Profile Selection
control Enable

8273

0x2051

R/W

0 = HMI or Comms selection
1 = Digital input profile selection

Current Mode
Selected

8280

0x2058

RO

0 = Mode Selection

1 = Configuration

2 = Manual

3 = Timer

4 = Profile

2.8.2. Manual Mode Parameters

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Manual Mode
Recovery

8278

0x2056

R/W

0 = Control Off
1 = Recover to Mode

Manual Mode
recovery Time

8279

0x2057

R/W

Value in seconds

Manual Mode
Status

8281

0x2059

RO

0 = Mode Stopped
1 = Mode Running

Manual Mode
Relay Status

2170

0x087A

RO

Bit 0 = Relay 1
Bit 1 = Relay 2
Bit 2 = Relay 3
Bit 3 = Relay 4
Bit 4 = Relay 5

Manual Mode
Control

8283

0x205B

R/W

0 = Stop Manual Mode
1 = Start Manual Mode
3 = Waiting for Command

Manual Mode
Control Setpoint

3960

0x0F78

R/W

Manual Mode
Relay 1

8249

0x2039

R/W

0 = Off
1 = On

Manual Mode
Relay 2

8250

0x203A

R/W

0 = Off
1 = On

Manual Mode
Relay 3

8251

0x203B

R/W

0 = Off
1 = On