Modbus Programming Manual

20

Version 2

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.

Parameter
Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

11

Cycle Complete

12

Profile Running

13

Or of Alarms

14

Alarm and Events

Alarm Selection

2218

0x08AA

R/W

Value

Selection

0

Alarm 1 or Alarm 2

1

Alarm 1 or Alarm 2 or Alarm 3

2

Alarm 1 or Alarm 2 or Alarm 3 or
Alarm 4

3

Alarm 1 or Alarm 2 or Alarm 3 or
Alarm 4 or Alarm 5

Event Alarm
Selection

2220

0x08AC

R/W

Value

Selection

0

Alarm 1 or Event 1

1

Alarm 2 or Event 2

2

Alarm 3 or Event 3

3

Alarm 4 or Event 4

4

Alarm 5 or Event 5


2.2.6. Linear Output Parameters

Parameter
Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Linear Output
Usage

2144

0x0860

R/W

Value

Usage

0

None

1

Retransmit PV

2

Retransmit SP

3

Primary (Heat) Control Power

4

Cool Control Power (Only available on
Heat Cool model)

Linear output
range

2223

0x08AF

R/W

Value

Range

0

0

– 5V

1

0

– 10V

2

2

– 10V

3

0

– 20mA

4

4

– 20mA

Retransmit
Minimum

2152

0x0868

R/W

Retransmit
Maximum

2153

0x0869

R/W