Alarm 5, High limit alarm parameters – Despatch Protocol 3 Modbus Communications User Manual

Page 26

Advertising
background image

A

BOUT

T

HIS

M

ANUAL

Modbus Programming Manual

26

Version 2

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

alarms 4 and 5.

Alarm Hysteresis

6194

0x1832

R/W

Limited by the span of the input range

Alarm inhibit

6195

0x1833

R/W

0 = Disabled
1 = Enabled

Alarm status

6196

0x1834

R

0 = Inactive
1 = Active

Alarm inhibit
status

6197

0x1835

R

0 = Not inhibited
1 = Inhibited

Rate Minimum
Time Alarm
Value

6198

0x1836

R/W

2.5.5. Alarm 5

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Alarm Type

6208

0x1840

R/W

0 = High Alarm
1 = Low Alarm
2 = Deviation Alarm
3 = Band Alarm
4 = Loop Alarm
5 = Sensor Break Alarm

Alarm Value

6209

0x1841

R/W

Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the span of the
input range for alarm types 2 and 3. Not used for
alarms 4 and 5.

Alarm Hysteresis

6210

0x1842

R/W

Limited by the span of the input range

Alarm inhibit

6211

0x1843

R/W

0 = Disabled
1 = Enabled

Alarm status

6212

0x1844

R

0 = Inactive
1 = Active

Alarm inhibit
status

6213

0x1845

R

0 = Not inhibited
1 = Inhibited

Rate Minimum
Time Alarm
Value

6214

0x1846

R/W

2.5.6. High Limit Alarm Parameters

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Alarm Value

9022

0x233E

R/W