Timer mode parameters – Despatch Protocol 3 Modbus Communications User Manual

Page 33

Advertising
background image

ADDRESS LIST

Modbus Programming Manual

33

Version 2

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Manual Mode
Relay 4

8252

0x203C

R/W

0 = Off
1 = On



2.8.3. Timer Mode Parameters

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Timer Mode
Recovery

8275

0x2053

R/W

0 = Control Off
1 = Restart Timer
2 = Continue Timer

Timer Mode
Recovery Time

8276

0x2054

R/W

Value in seconds

Timer Mode Auto
Hold Value

8272

0x2050

R/W

Timer Mode
Status

8282

0x205A

RO

0 = Mode Stopped
1 = Mode Running

Timer Mode
Relay Status

2170

0x087A

RO

Bit 0 = Relay 1
Bit 1 = Relay 2
Bit 2 = Relay 3
Bit 3 = Relay 4
Bit 4 = Relay 5

Timer Mode
Control

8284

0x205C

R/W

0 = Stop Timer
1 = Start Timer
3 = Waiting for Command

Timer Time

8270

0x204E

R/W

Time in seconds

Current
Remaining Time
of timer

8238

0x202E

RO

Value in seconds. The amount of time remaining
for the active segment.

Timer Mode
Control Setpoint

3960

0x0F78

R/W

Timer Mode
Relay 1

8249

0x2039

R/W

0 = Off
1 = On

Timer Mode
Relay 2

8250

0x203A

R/W

0 = Off
1 = On

Timer Mode
Relay 3

8251

0x203B

R/W

0 = Off
1 = On

Timer Mode
Relay 4

8252

0x203C

R/W

0 = Off
1 = On


Advertising