Segment Type

Segment Info

Description

A

B

1 = Time of day

Start Time

Wait until time of the day “B” in seconds since
midnight.

Loop

Number of times to
repeat 1 to 9999

Segment number

Loop to the specified segment number “B” from this
point. Repeat this “A” times. Only segments below the
current segment can be entered. Two loops must not
cross each other.

Join

Null

Profile number

On completion of this

profile jump run profile “B”

End

0 = Control off

Null

Turn off all control outputs.

1 = Maintain profile
setpoint

Null

Stay at the final setpoint of the profile

2 = Control off with
events

Null

Turn off the outputs but maintain the events.

Repeat
Sequence Then
End

0 = Outputs off

Number of times to
repeat sequence

Repeat the profile sequence number “B” times, then
turn off the control outputs

1 = Maintain profile
setpoint

Repeat the profile sequence number “B” times, then
hold the last profile setpoint.

2 = Control off with
events

Turn off the outputs but maintain the events.

2.9.5.6. Deleting Profiles (Command Code DP and DA)

An individual profile can be deleted, or all profiles can be cleared with a single message.
Deleting a profile removes the header of the specified profile and any segments associated with it.
Delete all profiles wipes all profiles and segments from the instrument.

Delete Profiles - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument.

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

06

06

Read Quantity Of Registers High

00

00

Read Quantity Of Registers Low

01

01

Write Start Address High

32

20

Write Start Address Low

06

06

Write Quantity Of Registers High

00

00

Write Quantity Of Registers Low

02 or 01

02 or 01

Delete A Profile (DP) = 02dec / 0x02hex
Delete All Profiles (DA) = 01dec / 0x01hex

Byte Count

04 or 02

04 or 02

Delete A Profile (DP) = 04dec / 0x04hex
Delete All Profiles (DA) = 02dec / 0x02hex

Command Code High Byte

68

44

Delete A Profile (DP) = 17488dec /
0x4450hex
Delete All Profiles (DA) = 17473dec /
0x4441hex

Command Code Low Byte

80 or 65

50 or 41

Profile Number High Byte

A/R

A/R

Note: The profile number is not included
in the message when deleting all profiles.

Profile Number Low Byte

A/R

A/R

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

The instrument replies to this message with an Edit Response Message Section 2.9.5.9.