Logger parameters (data logger), Data recorder, Real time clock – Despatch Protocol 3 Modbus Communications User Manual

Page 28

Advertising
background image

A

BOUT

T

HIS

M

ANUAL

Modbus Programming Manual

28

Version 2

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any means
including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and retrieval systems without
the written permission of Despatch Industries, unless for purchaser's personal use.

2.6. Logger parameters (Data Logger)

2.6.1. Data Recorder

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Log Interval

7550

0x1D7E

R/W

0 = Every second
1 = Every 2 seconds
2 = Every 5 seconds
3 = Every 10 seconds
4 = Every 15 seconds
5 = Every 30 seconds
6 = Every Minute
7 = Every 2 Minutes
8 = Every 5 Minutes
9 = Every 10 Minutes
10 = Every 15 Minutes
11 = Every 30 Minutes
12 = Every 60 Minutes

Log Mode

7551

0x1D7F

R/W

0 = Record until memory used
1 = Continues FIFO

Memory
Remaining

7554

0x1D82

R

In Bytes

Time Remaining

7555

0x1D83

R

In seconds

2.6.2. Real Time Clock

Parameter Name

Modbus
Address
(Dec)

Modbus
Address
(Hex)

Access
R/W

Notes

Date format

7868

0x1EBC

R

0 = dd/mm/yyyy (European Default)
1 = mm/dd/yyyy (USA Default)

Time

7869

0x1EBD

R/W

In seconds from midnight

Date

7870

0x1EBE

R/W

Day of the week

7872

0x1EC0

R/W

1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday

Advertising