Read a segment (command code rs) – Despatch Protocol 3 Modbus Communications User Manual

Page 47

Advertising
background image

Modbus Programming Manual

A

DDRESS LIST

Version 2

47

Copyright © 2012 by Despatch Industries.

All rights reserved. No part of the contents of this manual may be reproduced, copied or transmitted in any form or by any
means including graphic, electronic, or mechanical methods or photocopying, recording, or information storage and
retrieval systems without the written permission of Despatch Industries, unless for purchaser's personal use.

Read Profile Header - Response (from instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Profile Name Character 7

A/R

A/R

used to fill any unused characters at the end
of the name.


Characters 9 to 16 are not used so can be
ignored.

Profile Name Character 8

A/R

A/R

Profile Name Character 9

32

20

Profile Name Character 10

32

20

Profile Name Character 11

32

20

Profile Name Character 12

32

20

Profile Name Character 13

32

20

Profile Name Character 14

32

20

Profile Name Character 15

32

20

Profile Name Character 16

32

20

Profile Start Signal High Byte

00

00

0 = No delay, 1 = After delay, 2 = At
Time/day

Profile Start Signal Low Byte

A/R

A/R

Profile Start Time (Byte 4 - High)

Floating point number

Profile Start Time (Byte 3)

Profile Start Time (Byte 2)

Profile Start Time (Byte 1 - Low)

Profile Start Day High Byte

00

00

1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday, 10 = Saturday And
Sunday, 11= All Week

Profile Start Day Low Byte

A/R

A/R

Profile Starting Setpoint High

00

00

1 = Current Process Variable Value

Profile Starting Setpoint Low

A/R

A/R

Profile Recovery High Byte

00

00

0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint,
4 = Continue profile from where it was when
power failed

Profile Recovery Low Byte

A/R

A/R

Profile Recovery Time (Byte 4 - high)

Floating point number

Profile Recovery Time (Byte 3)

Profile Recovery Time (Byte 2)

Profile Recovery Time (Byte 1 - Low)

Profile Abort action High Byte

00

00

0 = Control to off
1 = Maintain last profile setpoint

Profile Abort Action Low Byte

A/R

A/R

Profile Cycles High Byte

A/R

A/R

1 to 9999 or 10,000 for “Infinite”

Profile Cycles Low Byte

A/R

A/R

CRC High Byte

A/R

A/R

CRC Low Byte

A/R

A/R

2.9.5.11. Read a Segment (Command Code RS)

Read A Segment - Request (to instrument)

Field Name

Data

Comments

(Dec)

(Hex)

Unit Address

A/R

A/R

The ID address of the instrument

Function Code

23

17

Requires the multi read/write function

Read Start Address High Byte

32

20

Read Start Address Low Byte

06

06