DETECTION COvERAGE
The FlexSonic Acoustic Detector is an omni-directional

acoustic analyzer that can recognize the unique

frequency content of events such as gas leaks. The

high-frequency sound energy generated by pressurized

gas escaping is dependent upon several factors such

as gas pressure, geometry of the leak opening, gas

viscosity, as well as environmental conditions such as

temperature and humidity.

It is recommended that the detector be mounted

above the potential leak sources in the coverage area

to minimize attenuation of acoustic signal from the

detector housing itself. Also, care should be taken to

eliminate acoustic blind spots caused by equipment,

scaffolding, etc. that lie between the detector and

potential leak sources.

Background noise can also diminish the effective

coverage area, however, the patented Learn function

allows the FlexSonic Acoustic Detector to ignore many

sources of high frequency sound energy without

negatively impacting detection range (e.g. moving

the detector, or raising the alarm threshold level). For

best performance, it is recommended that the acoustic

environment where the detector is to be placed be

captured with either the onboard learn function or

data logging capabilities of the FlexSonic Acoustic

Detector. The acoustic profile generated can be used

to very accurately display the exact content/sources of

background noise, and optimize the alarm threshold

setting. Refer to the Data Management and Profile

Mode sections of this manual for additional information

on alarm settings.

Detection range will vary depending upon the leak

rate, environment, and installation factors described.

Reference detection ranges for the FlexSonic Acoustic

Detector are provided below (detector mounted 2

meters above ground pointing vertically downwards,

and low ambient background noise > 20 kHz):

leak Source:
Leak Rate:

0.004 Kg/Sec

Gas Type:

Compressed Air

Gas Pressure:

6 Bar (87 psi)

Leak Orifice:

2 mm round

Orientation:

Straight up

Detection coverage is specified as a radius with the leak

source at or below detector level, and unobstructed by

infrastructure.

Basic Mode, 50 dB setting =

12 meter radius (40 feet)

Profile Mode (4 dB above background) =

20 meter radius (66 feet)

For information regarding installation of the FlexSonic

Acoustic Detector in a specific application, please

contact the Det-Tronics factory.

= PROFILE MODE

= BASIC MODE

3m

6m

9m

12m

15m

18m

21m

A2611

Coverage Range of FlexSonic Acoustic Detector (low level leak)

Advertising
This manual is related to the following products: