M25 Models
M25 models have straight threads and a removable

connector assembly with lock nut. Install the sensor

as follows:

1. Remove the connector assembly from the AC100

Sensor. See Figure 9.

2. Screw the lock nut as far back as it will go (finger

tight only), then screw the connector assembly into

the appropriate entry on the termination box. A light

coating of grease on the threads is recommended.

3. Screw the assembly into the termination box as far

as it will go and tighten with a 35mm socket wrench.

4. Tighten the lock nut against the termination box.

See Figure 10.

5. Insert the sensor wires through the connector

assembly into the termination box, then secure the

sensor to the termination box by tightening the ring

on the connector assembly. Prior to tightening the

ring, orient the sensor with the set screw away from

the detector mounting surface to ensure adequate

clearance between the sensor and mounting

surface. See Figure 8.

6. Tighten the connector ring, then install set screws to

prevent movement.

Note

there are a total of six set screw holes on the
connector ring, three on the lower level and three
on the upper level. Install at least one set screw
on each level. See Figure 11.

Figure 8—AC100 Connected to Termination box

(m25 model Shown)

ORIENT SET SCREW AWAY FROM
MOUNTING SURFACE TO ENSURE
ADEQUATE CLEARANCE BETWEEN
SENSOR AND SURFACE

A2618

Figure 9—AC100 with Connector Assembly Removed

AC100 SENSOR

CONNECTOR ASSEMBLY

SCREW THE LOCK NUT AS FAR BACK AS POSSIBLE

(FINGER TIGHT ONLY)

A2619