2.5

95-8657

24

PASSWORD PROTECTION
The ATX10 allows the use of a password for restricting

changes to configuration parameters and limiting

access to safety critical commands.

The ATX10 is shipped from the factory with the password

protection (Write Protect) feature enabled. Refer to the

AC100/ATX10 HART Addendum (number 95-8698) for

complete information regarding use of the Write Protect

feature.

General applicatiOn

inFOrmatiOn

NUISANCE SOURCES
Most industrial or processing environments are

relatively free from the higher frequency sound energy

that is characteristic of a gas leak, however, there are

instances where high frequency nuisance sources

exist. The sources may include, but are not limited to:
• Rotating machinery / gear meshes
• Bearings/fans motors
• Metal-to-metal contact / chains
• High velocity wind through rigging

The FlexSonic Acoustic Detector can be effectively

employed to record the acoustic background

environment unique to an installation and provide a

clear display of the information using the Acoustic

Inspector software package. The ability to view the

actual acoustic environment enables users of the

FlexSonic Acoustic Detector to make intelligent, data-

based decisions on how to best address nuisance

sources in the alarm profile.

FRIENDLY LEAkS
The FlexSonic Acoustic Detector recognizes the

acoustic signature of pressurized gas escaping.

Therefore, so called ‘friendly’ sources of compressed

gas leaks such as air lines and relief stacks may be

detected as well.

While some non-hazardous pressurized gas escapes

may be effectively ignored through the patented learn

function, the expected hazardous leak SPL must

be greater than the non-hazardous leak SPL for the

detector to effectively discriminate between the two

sources.

If the time duration of the non-hazardous source is

relatively short, the user settable alarm delay setting

can be adjusted to reject short duration leaks. Refer

to the “Operation” section of this manual for details on

alarm adjustments.

Advertising