Det-Tronics ATX10 Transmitter User Manual

Page 18

Advertising
background image

2.5

95-8657

16

WIRING PROCEDURE
Ensure that all cables are terminated properly.

Conductor insulation should be stripped off with a bare

conductor length of 0.2 inch (5 mm) minimum and 0.7

inch (18 mm) maximum. Ensure that cable shield is

properly terminated and that bare shield wire is not

allowed to accidentally contact the metal housing or

any other wire.

impOrTanT

the AC100 GND wire (green, 16 AWG, 1.31 mm

2

)

must be properly grounded inside the StB
or AtX10 to maintain proper Intrinsic Safety
connections. A lug is provided and must be
properly crimped to the wire and secured with
the provided screw and washer at the location
marked by the GND symbol. the AC100 and the
adjoining StB/AtX10 are also provided with an
external GND connection (lug screw and washer
provided) that must be bonded to a suitable earth
GND connection. In addition, the power supply
GND must be terminated at the StB/AtX10 to
ensure 1 ohm or less resistance.

Figure 12 shows the wiring terminals on the ATX10

Transmitter.

Figure 13 shows an AC100 wired directly to an ATX10

Transmitter.

Figure 14 shows an AC100 connected to an STB

termination box and wired to an ATX10 Transmitter.

Figure 15 shows power and signal wiring for an ATX100

wired to a PLC.

Figure 16 shows an ATX10 with AC100 wired to a FlexVu

UD10 Universal Display.

See Figure 17 for benchtop test wiring.

Note

For proper HARt communication, a signal loop
resistance of 250 ohms must be present at the
4-20 mA output terminals.

Figure 10—Connector Assembly Attached to Termination box

TIGHTEN LOCK NUT AGAINST TERMINATION BOX

TIGHTEN WITH 35MM SOCKET WRENCH

A2620

Figure 11—Set Screw locations on Connector Ring

SET SCREWS

A2621