Det-Tronics ATX10 Transmitter User Manual
Page 20
Advertising

2.5
95-8657
18
Figure 14—AC100 Acoustic Sensor Connected to STb and wired to ATX10 Transmitter
NOTES: DEVICE HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.
CONNECT THE GREEN WIRE FROM THE AC100 TO THE GROUND SCREW
INSIDE THE STB HOUSING. EARTH GROUND CONNECTION REQUIRED.
SHIELDED TWISTED PAIR IS RECOMMENDED FOR SIGNAL WIRING,
500 FEET MAXIMUM.
ATX10
TRANSMITTER
BOARD
A2607
STB TERMINATION BOX
AC100
ACOUSTIC
SENSOR
RED
BLA
CK
GR
A
Y
OR
ANGE
J3-1
J3-2
J3-3
J3-4
J3-5
A
B
24
VDC +
24
VDC –
SHIELD
P1
-4
P1
-3
P1
-2
P1
-1
24
VDC +
4-20 mA
24
VDC –
SHIELD
P3-4
P3-3
P3-2
P3-1
JUMPER
TO GND
GND
B
A
POWER
AND OUTPUT
SENSOR
ORANGE
GRAY
RED
BLACK
GREEN
INTERFACE
TO SOFTWARE
CONFIGURATOR
IS GROUND
Advertising
This manual is related to the following products: