Det-Tronics ATX10 Transmitter User Manual

Page 34

Advertising
background image

2.5

95-8657

32

appenDix D

IECEx APPROvAL DESCRIPTION

IEC Standards:
IEC60079-0: 2011

Electrical apparatus for explosive atmospheres, General Requirements

IEC60079-1: 2007

Electrical apparatus for explosive atmospheres, Flameproof enclosure “d”

IEC60079-11: 2011

Intrinsic Safety explosive atmospheres Equip protection by Intrinsic Safety

IEC60079-31: 2008

Explosive atmospheres Equip. Dust Ignition Protection by enclosure “t”

IEC60529: 2001

Degrees of Protection Provided by Enclosures (IP Code)

IEC Special Conditions for Safe Use (X):

AC100
• The AC100 Acoustic Sensor must always be installed with the detection head pointing down vertically.
• The AC100 Acoustic Sensor must only be installed in areas where there is a low risk of mechanical damage.
• The AC100 is only to be used connected to the ATX10 Acoustic Transmitter or Model STB Sensor Termination Box.

ATX10
• The ATX10 must only be installed in areas where there is a low risk of mechanical damage.

Warning

Always ensure that the detector/junction box hazardous (classified) location ratings are applicable for the
intended use.

Additional Safety Notes:

• The following warning is on the product: Warning: Do not open when an explosive gas atmosphere may be

present. For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For

temperature below –10°C use suitable field wiring for the lowest temperature.

• Cable, bushings and the conduit entries shall be of a flameproof type already certified according to relevant IEC

standard, rated IP66, so the protection principle employed will not be impaired.

• Unused conduit entries shall be closed using flameproof stop plugs certified for the conditions of use (IP66

minimum). The stop plugs should be removable only with the aid of a tool.

• Shielded cable is required.

AC100
IECEx ULD13.0002X

Ex d ib IIC T4 Gb

Ex tb IIIC T80°C Db

Tamb: –55°C to +75°C

IP66

ATX10
IECEx ULD13.0003X

Ex d IIC T6 Gb

Ex tb IIIC T80°C Db

Tamb: –55°C to +75°C

IP66