maintenance

impOrTanT

Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of
the flamepaths.

the AC100 Sensor contains no user serviceable
components and should never be opened. the
AtX10 wiring compartment is the only part of the
acoustic detector that should be opened by the
user in the field.

Note

Refer to the FlexSonic Acoustic Detector Safety
Manual 95-8658 for specific requirements and
recommendations applicable to the proper
installation, operation, and maintenance of all
SIL-Certified acoustic detectors.

To maintain maximum sensitivity and detection range,

the AC100 Acoustic Sensor cover (and optional

foam insert) must be kept relatively clean and free of

debris. Refer to the following procedure for cleaning

instructions.

ROUTINE INSPECTION
Periodically or during scheduled maintenance, the

AC100 cover should be inspected to ensure that

obstructions such as plastic bags, litter, heavy oil and

tar, paint, mud, snow, or other materials do not block

sound from reaching the sensor and thereby impairing

the performance of the device.

When using the optional foam insert in dirty or dusty

environments, check to ensure the insert is clean and

free of buildup. Replace the insert if torn or damaged.

CLEANING
To clean the AC100 Acoustic Sensor cover, ensure that

the device is powered off, then simply grasp the cover

assembly and twist counterclockwise. See Figure 18.

The stainless steel mesh can be cleaned with warm

soapy water and rinsed. Remove any excess water

with a cloth, then air dry.

The foam insert (if used) can also be cleaned with

warm, soapy water and rinsed. Hand wring any excess

water by simply squeezing the foam insert to remove

excess water.

When re-installing the foam insert / AC100 cover, use

care not to over tighten.

CaUTiOn

the AC100 sensor head (microphone and AIC
acoustic source) does not require cleaning
and should not be contacted with any cleaning
materials.

Figure 18—Acoustic Detector with protective Sensor Cover Removed

FOAM INSERT

SENSOR COVER

MICROPHONE

AC100 SENSOR

ATX10 TRANSMITTER

AIC ACOUSTIC SOURCE

A2615

NO SERVICEABLE COMPONENTS

WITHIN SENSOR HOUSING.

DO NOT OPEN.