startup proceDure

When installation of the equipment is complete, perform

the “Fire Alarm Test” below.

FIRE ALARM TEsT
1. Disable any extinguishing equipment that is

connected to the system.

2. Apply input power to the system.
3. Initiate an oi test. (See “Magnetic oi / Manual oi

under Optical Integrity in the Description section of

this manual.

4. Repeat this test for all detectors in the system. If

a unit fails the test, refer to the “Troubleshooting”

section.

5. Verify that all detectors in the system are properly

aimed at the area to be protected. (Det-Tronics'

Q1201C Laser Aimer is recommended for this

purpose.)

6. Enable extinguishing equipment when the test is

complete.

troubleshooting

WarnIng

The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

1. Disable any extinguishing equipment that is

connected to the unit.

2. Inspect the viewing windows for contamination and

clean as necessary. (Refer to the “Maintenance”

section for complete information regarding cleaning

of the detector viewing windows.)

3. Check input power to the unit.
4. If the fire system has a logging function, check the

fire panel log for output status information. See Table

3 for information regarding 0 to 20 mA output.

5. Turn off the input power to the detector and check all

wiring for continuity. Important: Disconnect wiring

at the detector before checking system wiring for
continuity.

6. If all wiring checks out and cleaning of the oi plate/

window did not correct the fault condition, check for

high levels of background IR radiation by covering

the detector with the factory supplied cover or

aluminum foil. If the fault condition clears, extreme

background IR radiation is present. Re-adjust the

view of the detector away from the IR source or

relocate the detector.

If none of these actions corrects the problem, return the

detector to the factory for repair.

NOTE

It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.

maintenance

Important

Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.

WarnIng

The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

table 3—current Level output troubleshooting guide

1If fault continues, return device to factory for repair.

2See “Maintenance” section for cleaning procedure.

Current Level

(±0.3 mA)

status

Action

0 mA

Power Fault

Check system wiring.

1 mA

General Fault

Cycle power.

1

2 mA

oi Fault

Clean windows.

2

4 mA

Normal Operation

16 mA

Hi Background IR

Fault

Remove IR source or

aim detector away

from IR source.

20 mA

Fire Alarm