95-8554

22

11.1

FM Approval and performance Report – Continued

FIELD OF VIEW

Very High sensitivity, Quick Fire Off

Fuel

size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)*

Vertical

(degrees)

Typical Vert. Response

Time (seconds)*

n-Heptane

1 x 1 foot

42.5

(13)

+45

–45

12

14

+45

–30

10

16

Methane

32 inch plume

30

(9.1)

+45

–45

7

4

+45

–30

6

4

High sensitivity, TDsA On, Quick Fire Off

Fuel

size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)*

Vertical

(degrees)

Typical Vert. Response

Time (seconds)*

n-Heptane

1 x 1 foot

25

(7.6)

+45

–45

7

7

+45

–30

6

5

Methane

32 inch plume

17.5

(5.3)

+45

–45

6

3

+45

–30

4

4

High sensitivity, TDsA On, Quick Fire On

Fuel

size

Distance

feet (m)

Horizontal

(degrees)

Typical Horiz. Response

Time (seconds)*

Vertical

(degrees)

Typical Vert. Response

Time (seconds)*

Black

Powder

40 Grams

5

(1.5)

+45

–45

0.04

0.03

+45

–30

0.04

0.04

*Add 2 seconds for EQP model.

FALsE ALARM IMMuNITy

High sensitivity, TDsA On, Quick Fire Off

False Alarm souce

Distance feet

(m)

Modulated Response

unmodulated Response

Sunlight, direct, reflected

—

No alarm

No alarm

Vibration

NA

No alarm

No alarm

Arc welding

15 (4.6)

No alarm

No alarm

70 w sodium vapor lamp

3 (0.9)

No alarm

No alarm

250 w mercury vapor lamp

3 (0.9)

No alarm

No alarm

300 w incandescent lamp

3 (0.9)

No alarm

No alarm

500 w shielded quartz halogen lamp

3 (0.9)

No alarm

No alarm

1500 w electric radiant heater

10 (3)

No alarm

No alarm

Two 34 w fluorescent lamps

3 (0.9)

No alarm

No alarm

*Add 2 seconds for EQP model.

*Add 2 seconds for EQP model.