11.1

FACTORs INHIbITINg DETECTOR REspONsE
Windows
Glass and Plexiglas windows significantly attenuate

radiation and must not be located between the detector

and a potential flame source. If the window cannot be

eliminated or the detector location changed, contact

Det-Tronics for recommendations regarding window

materials that will not attenuate radiation.

Obstructions
Radiation must be able to reach the detector in order

for it to respond. Care must be taken to keep physical

obstructions out of the line of view of the detector.

smoke
Smoke will absorb radiation. If accumulations of dense

smoke can be expected to precede the presence of a flame,

then detectors that are used in enclosed areas should be

mounted on the wall approximately 3 feet (0.9 m) from the

ceiling where the accumulation of smoke is reduced.

Detector Viewing Windows
It is important to keep the detector viewing windows as

free of contaminants as possible in order to maintain

maximum sensitivity. Commonly encountered substances

that can significantly attenuate IR radiation include, but

are certainly not limited to, the following:

Dust and dirt buildup

Paint overspray

Water and ice

important safety notes

WarnIng

Do not open the detector assembly in a hazardous

area when power is applied. The detector contains

limited serviceable components and should never

be opened. Doing so could disturb critical optical

alignment and calibration parameters, possibly

causing serious damage.

CaUtIon

The wiring procedures in this manual are intended

to ensure proper functioning of the device under

normal conditions. However, because of the

many variations in wiring codes and regulations,

total compliance to these ordinances cannot be

guaranteed. Be certain that all wiring complies

with the NEC as well as all local ordinances. If

in doubt, consult the authority having jurisdiction

before wiring the system. Installation must be

done by a properly trained person.

CaUtIon

To prevent unwanted actuation or alarm,

extinguishing devices must be disabled prior to

performing detection system tests or maintenance.

CaUtIon

The IR flame detectors are to be installed in places
where the risk of mechanical damage is low.

attEntIon

Remove the protective cap from the front of the

detector before activating the system.

attEntIon

Observe precautions for handling electrostatic

sensitive devices.