Appendix a, Fm approval and performance report – Det-Tronics X9800 IR Flame Detector User Manual

Page 22

Advertising
background image

95-8554

20

11.1

appenDiX a

FM AppROVAL AND pERFORMANCE REpORT

THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:

• Explosion-proof for Class I, Div. 1, Groups B, C and D (T5) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T5) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA/Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).

Flameproof per ANSI/ISA 60079-0, -1, -7

for Class I, Zone 1 -

AEx d e IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)

AEx d IIC Gb; T6 (Tamb –40°C to +60°C); T5 (Tamb –40°C to +75°C)

for Zone 21 -

AEx tb T80°C

Tamb –40°C to +75°C

Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.

The following accessories are FM approved for use with the X9800 Flame Detector:

part Number

Description

102740-002

Magnet

007739-001

Magnet and Extension Pole

007290-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors

007290-002

Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only

011385-001

Q9033 Collar Attachment

The following performance criteria were verified:

AuTOMATIC OpTICAL INTEgRITy TEsT:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces

resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated

Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector

was verified to detect a fire.

MANuAL OpTICAL INTEgRITy TEsT:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm

relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.

The oi test procedure, as described in the "Magnetic oi / Manual oi" section of this instruction manual, is the approved

external optical test method for this detector to verify end-to-end detector function. This test replaces the function and

need of a traditional external test lamp.