Det-Tronics X9800 IR Flame Detector User Manual

Page 9

Advertising
background image

7

95-8554

11.1

pROTECTION AgAINsT MOIsTuRE DAMAgE
It is important to take proper precautions during

installation to ensure that moisture will not come in

contact with the electrical connections or components

of the system. The integrity of the system regarding

moisture protection must be maintained for proper

operation and is the responsibility of the installer.

If conduit is used, we recommend installing drains,

according to local codes, at water collection points

to automatically drain accumulated moisture. It is

also recommended to install at least one breather,

according to local codes, at upper locations to provide

ventilation and allow water vapor to escape.

Conduit raceways should be inclined so that water

will flow to low points for drainage and will not collect

inside enclosures or on conduit seals. If this is not

possible, install conduit drains above the seals to

prevent the collection of water or install a drain loop

below the detector with a conduit drain at the lowest

point of the loop.

Conduit seals are not required for compliance with

explosion-proof installation requirements, but are

highly recommended to prevent water ingress in

outdoor applications. Units with M25 threads must use

an IP66/IP67 washer to prevent water ingress.

WIRINg pROCEDuRE
Wire size and Type
The system should be wired according to local codes.

The wire size selected should be based on the

number of detectors connected, the supply voltage

and the cable length. Typically 16 AWG or 2.5 mm

2

shielded cable is recommended. Wires should be

stripped 3/8 inch (9 mm). A minimum input voltage

of 18 Vdc must be present at the X9800.

NOTE

Re fe r to “ Powe r C o n s u m p t i o n” i n t h e
“Specifications” section of this manual.

The use of shielded cable is required to protect against

interference caused by EMI and RFI. When using cables

with shields, terminate the shields as shown in Figures

7 through 12, and Figure 15. Consult the factory if not

using shielded cable.

In applications where the wiring cable is installed in

conduit, the conduit must not be used for wiring to other

electrical equipment.

If disconnection of power is required, separate disconnect

capability must be provided.

CaUtIon

Installation of the detector and wiring should be
performed only by qualified personnel.

Detector Mounting
Install the mounting arm assembly on a rigid surface.

The ideal installation surface should be free of vibration

and suitable to receive 3/8 inch (M9) bolts with a length

of at least 1 inch (25 mm). The surface must also have

sufficient capacity to hold the detector and mounting

arm weights (See "Specifications" section). Refer to the

Q9033 Mounting Arm manual (95-8686) for additional

mounting information. See Figure 3 for dimensions.

13.1

(33.4)

10.6

(27.0)

4.0

(10.2)

4.0

(10.2)

3.0

(7.6)

3.0

(7.6)

4X ø0.42

(1.1)

E2069

NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.

figure 3—Q9033 mounting arm without collar attachment Dimensions in inches (cm)

(see figure 1 for correct Detector orientation .)