Instructions ir flame detector x9800 – Det-Tronics X9800 IR Flame Detector User Manual

Page 3

Advertising
background image

1

95-8554

11.1

Important

Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.

attEntIon

The X9800 includes the Automatic

oi

® (Optical

Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
testing with an external test lamp is not
approved or required
.

Description

The X9800 Single Frequency IR Flame Detector meets the

most stringent requirements worldwide with advanced

detection capabilities and immunity to extraneous

sources, combined with a superior mechanical design.

The detector is equipped with both automatic and manual

oi test capability. The detector has Division and Zone

explosion-proof ratings and is suitable for use in indoor

and outdoor applications.

The standard output configuration includes fire, fault and

auxiliary relays. Output options include:

0 to 20 mA output (in addition to the three relays)

Pulse output for compatibility with existing Detector

Electronics Corporation (Det-Tronics

®

) controller

based systems (with fire and fault relays)

Eagle Quantum Premier® (EQP) compatible model

(no analog or relay outputs)

HART communication

A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm or

fault conditions.

Microprocessor controlled heated optics increase

resistance to moisture and ice.

The X9800 housing is available in copper-free aluminum

or stainless steel, with NEMA/Type 4X and IP66/IP67

rating.

OuTpuTs
Relays
The standard detector is furnished with fire, fault and

auxiliary relays. All three relays are rated 5 amperes

at 30 Vdc.

The Fire Alarm relay has redundant terminals and

normally open / normally closed contacts, normally

de-energized operation, and latching or non-latching

operation.

The Fault relay has redundant terminals and normally

open contacts, normally energized operation, and

latching or non-latching operation.

INsTRuCTIONs

ir flame Detector

X9800

©

Detector Electronics Corporation 2013

rev: 6/13