Det-Tronics X9800 IR Flame Detector User Manual

Page 4

Advertising
background image

95-8554

2

11.1

The Auxiliary relay has normally open / normally

closed contacts, and is configurable for energized or

de-energized operation, and latching or non-latching

operation.

0 to 20 mA Output
A 0 to 20 mA output is available as an option (in addition

to the three relays). This option provides a 0 to 20 mA dc

current output for transmitting detector status information

to other devices. The circuit can be wired in either an

isolated or non-isolated configuration and can drive

a maximum loop resistance of 500 ohms from 18 to

19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table 1

indicates the detector status conditions represented by

the various current levels. The output is calibrated at the

factory, with no need for field calibration. A model with

relays and 0-20 mA with HART is also available. Refer to

Addendum number 95-8637 for complete details.

NOTE

The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X9800. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status of
the LED always follows the status of the relays.

An alarm condition will normally over-ride a fault

condition, unless the nature of the fault condition

impairs the ability of the detector to generate or

maintain an alarm output, i.e. loss of operating power.

LON/sLC Output
The EQP model is designed for use exclusively with

Det-Tronics' Eagle Quantum Premier system. The

detector communicates with the system controller over

a digital communication network or LON/SLC (Local

Operating Network / Signaling Line Circuit). The LON/

SLC is a fault tolerant, two wire digital communication

network arranged in a loop configuration. Analog and

relay outputs are not available on this model.

LED
A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm or

fault conditions. Table 2 indicates the condition of the

LED for each status.

oi

(OpTICAL INTEgRITy)

Automatic

oi

The X9800 includes the Automatic oi feature — a

calibrated performance test that is automatically

performed once per minute to verify complete detector

operation capabilities. No testing with an external test

lamp is required. The detector automatically performs

the same test that a maintenance person with a test

lamp would perform — once every minute, 60 times per

hour. However, a successful Automatic oi test does not

produce an alarm condition.

The X9800 signals a fault condition when less than half

of the detection range remains. This is indicated by the

Fault output and is evident by the yellow color of the LED

on the face of the detector. See the "Troubleshooting"

section for further information.

Magnetic

oi / Manual oi

The detector also incorporates both Magnetic oi

(Mag oi) and Manual oi (Man oi) features that provide

the same calibrated test as the Automatic oi, and in

addition actuates the Alarm output to verify operation

for preventive maintenance requirements. These

features can be performed at any time and eliminate

the need for testing with a non-calibrated external test

lamp.

table 1—Detector status conditions indicated by current Level

table 2—Detector status indicator

Current Level (±0.3 mA)

Detector status

0 mA

Power Fault

1 mA

General Fault

2 mA

oi

Fault

4 mA

Normal Operation

16 mA

Pre-Alarm

20 mA

Fire Alarm

Detector status

LED Indicator

Power On/Normal Auto

oi

(no fault or fire alarm)

Green

Power On/Normal Man

oi

Green, flashing on for

0.5 sec. every 5 sec.

Fault

Yellow

Pre-Alarm/Background IR

Red, flashing on for

0.5 sec. and off for 0.5 sec.

Fire (Alarm)

Steady Red

On Power-Up, The LED Flashes in Sequence as Follows,

Indicating Sensitivity and Signal Processing Status

Low IR Sensitivity
Medium IR Sensitivity
High IR Sensitivity
Very High IR Sensitivity

One Green Flash

Two Green Flashes

Three Green Flashes

Four Green Flashes

Quick Fire/TDSA IR Signal
TDSA only IR Signal

One Yellow Flash

Two Yellow Flashes