Det-Tronics X9800 IR Flame Detector User Manual

Page 18

Advertising
background image

95-8554

16

11.1

features

• Responds to a fire in the presence of modulated

blackbody radiation (i.e. heaters, ovens, turbines)

without false alarm.

• High speed capability — 30 milliseconds.
• Built-in data logging / event monitoring, up to 1500

events (up to 1000 general, 500 alarms).

• Microprocessor controlled heated optics for

increased resistance to moisture and ice.

• Automatic, manual or magnetic oi testing.
• Easily replaceable oi plate.
• Fire, fault and auxiliary relays standard.
• 0 to 20 mA isolated output (optional).
• Eagle Quantum Premier LON/SLC output (optional).
• HART communication (optional)
• A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm

or fault conditions.

• Operates under adverse weather conditions.
• Mounting arm allows easy sighting.
• Integral wiring compartment for ease of installation.
• Explosion-proof/flame-proof detector housing. Meets

FM, CSA, ATEX and CE certification requirements.

• Class A wiring per NFPA-72.
• Meets NFPA-33 response requirement for under

0.5 second (available when model selected).

• 3 year warranty.
• Advanced signal processing (TDSA).
• RFI and EMC Directive compliant.

Associated Manuals
List of X9800 related manuals:

specifications

operating voLtage—

24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).

Maximum ripple is 2 volts peak-to-peak.

poWer consUmption—

Without heater: 2.1 watts at 24 Vdc nominal;

3.5 watts at 24 Vdc in alarm.

2.2 watts at 30 Vdc nominal;

4.0 watts at 30 Vdc in alarm.

Heater only: 8 watts maximum.

Total power:

16.5 watts at 30 Vdc with EOL resistor

installed and heater on maximum.

EOL resistor must be ceramic, wirewound type, rated

5 watts minimum, with actual power dissipation not to

exceed 2.5 watts.

For HART model, refer to Addendum number 95-8637.

poWer Up time—

Fault indication clears after 0.5 second; device is ready

to indicate an alarm condition after 30 seconds.

oUtpUt reLays—

Fire Alarm relay, Form C, 5 amperes at 30 Vdc:

The Fire Alarm relay has redundant terminals

and normally open / normally closed contacts,

normally de-energized operation, and latching or

non-latching operation.

Fault Alarm relay, Form A, 5 amperes at 30 Vdc:

The Fault relay has redundant terminals and

normally open contacts, normally energized

operation, and latching or non-latching operation.

Auxiliary relay, Form C, 5 amperes at 30 Vdc:

The auxiliary relay has normally open / normally

closed contacts, nor mally energized or

de-energized operation, and latching or non-

latching operation.

cUrrent oUtpUt (optional)—

0 to 20 milliampere (±0.3 mA) dc current, with a

maximum loop resistance of 500 ohms from 18 to

19.9 Vdc and 600 ohms from 20 to 30 Vdc.

Lon oUtpUt—

Digital communication, transformer isolated (78.5 kbps).

temperatUre range—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–67°F to +185°F (–55°C to +85°C).

Hazardous location ratings from –55°C to +75°C available

on flameproof model.

hUmiDity range—

0 to 95% relative humidity, can withstand 100%

condensing humidity for short periods of time.

TITLE

FORM NuMbER

Pulse

95-8555

EQP

95-8533

SIL 2 (Safety)

95-8672

HART Addendum

95-8637

Q9033 Mounting Arm

and Collar Attachment

95-8686

Inspector Monitor Software for

X-Series Flame Detectors

95-8581