2 device block state command (id 15) – INFICON SKY CDGxxxD (Profibus) User Manual

Page 26

Advertising
background image

26

tira54e1-a (2009-01) CDGxxxD.cp

There are a number of special commands for bringing the gauge into a status it
does not automatically go to.

ID Name

Structure Data type

Bytes Access

Store Range

15 Device

Block

State
Command

Simple UINT8

1 1_R/W

2_R/W

N

→ below

The device block state method allows the master to force the behavior of the
device block state machine (as shown in parameter device state) by setting it to
one of the values shown in the table below. Depending of the actual state, some
values may not be allowed at a time.

ID value

Name

Description

0 Inactive No

action.

1

Reset

Used for reinitializing the device.

2

Abort

Brings the device to the ABORT status.

3

Recover

Used for bringing the device from the ABORT
status into the Recovered State ≙ IDLE.

4

Execute

Brings the unit to the EXECUTING status, in which
the gauge functions normally. As soon as cyclic
data traffic is initialized, this status command is
executed automatically.

5

Stop

Brings the gauge to the IDLE status.

6 Perform

Diagnostic

Stops the running activity and starts SELFTEST.

7…127 Reserved

by

PNO

128…255 Manufacturer

specific


7.2.2 Device Block State

Command (ID 15)