3 installation, 1 electrical connection, Bus cable – JUMO 902910 CANtrans T RTD Temperature Probe with CANopen Output Operating Instructions User Manual
Page 10: Connection, Circular connector, Installation, Electrical connection

10
3 Installation
3.1
Electrical connection
Bus cable
- the bus specifications to ISO 11 898 must be observed
- cable diameter 6 to 12 mm
- conductor cross-section up to 1.5mm
2
per core
- signal cables must be routed separately from cables with voltages
above
60 V
- use cables with twisted cores
- avoid the vicinity of electrical installations, or use screened cables
Connection
Circular
connector
M12 x1; 5-pole to IEC 60 947-5-2
Earth the instrument at the pressure connection.
The bus ends must be provided with a line termination.
➩ Chapter 3 “Installation” / “Line termination”, page 11.
Connection
Terminal assignment
M12
connector
terminal box with
moulded cable
Sales No.
40/00337625
Supply voltage
10 — 30 V DC
CAN_V+
CAN_GND
2
3
white
blue
Output
CANopen
screen
CAN_H
CAN_L
1
4
5
brown
black
gray
1
5
4
2
3
2
5
3
1
4
Plug
Socket