4 Commissioning
4.1
Setting the CAN baud rate
General
The baud rate is set to 500 kbaud ex-factory.
The CAN baud rate can be set both via SDO telegrams (object dictionary) and
LSS.
Setting via SDO
The CAN baud rate can be reprogrammed via the CANopen object dictionary,
index 0x2001.
This setting will only be accepted as the new CAN baud rate after resetting the
transmitter.
Setting via LSS
CANtrans transmitters support the LSS standard (Layer Setting Services) as
per DSP-305, V1.1.
This can be used to set the baud rate and node ID for the entire plant in a stan-
dardized manner.
The LSS address of the transmitter is specified on the nameplate, so it is visi-
ble from the outside.
The latest setup tools from different manufacturers can also be used to oper-
ate this function.
As an alternative, the baud rate and node ID are also settable via SDO (see
above).
CAN baud rate
[kbaud]
Max. bus length
[m]
Entry in
object dictionary
0x2001
1000
25
0
800
100
1
500
100
2
250
250
3
200
250
99
125
500
4
100
500
98
50
1000
6
20
2500
7