Wiring the installation backplane

Important notes

5

l

46

EDK94ZPP0364 DE/EN/FR/ES/IT 2.1

5

Wiring the installation backplane

5.1

Important notes

{

Danger!

Dangerous electrical voltage

All power terminals remain live for up to three minutes after mains
disconnection.

Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes
before working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

{

Danger!

Dangerous voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event
of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor

diameter

³ 10 mm

2

or PE conductor must be connected twice)