5 terminal assignment, Wiring the installation backplane – Lenze E94AZPP User Manual

Page 54

Advertising
background image

Wiring the installation backplane

Wiring
Terminal assignment

5

l

54

EDK94ZPP0364 DE/EN/FR/ES/IT 2.1

5.3.5

Terminal assignment

I

Tip!

Complete the wiring of the installation backplane before plugging
in the standard device. The upper terminals of the installation
backplane cannot be connected with a plugged−in standard device.

Mains

Terminal X111
(left part)

Labelling

Description

L1
L2
L3

Connection of the mains phases
E94APNE0xx4/E94AZxPxxx4: L1, L2, L3
E94ARNE0xx4/E94AZMR0xx4xDB: L1.1, L2.1, L3.1

+

Terminal for the supply−side PE conductor with M5
ring cable lug

SSP940X111

Terminal X112
(right part)

Labelling

Description

L1
L2
L3

Connection of the mains phases
E94APNE0xx4/E94AZxPxxx4:

alternatively at the bottom L1, L2, L3

E94ARNE0xx4/E94AZMR0xx4xDB: L1.2, L2.2, L3.2

+

Terminal for the supply−side PE conductor with M5
ring cable lug

SSP940X112

Terminal data

Max. conductor cross−section

Tightening torque

!

[mm

2

]

[AWG]

[Nm]

[lb−in]

Device sizes 1+2:
flexible
with wire end
ferrule

2.5

12

0.5 ... 0.6

4.5 ... 6.2

PZ0

Device size 3:
flexible
with wire end
ferrule

10

6

1.2 ... 1.5

10.6 ... 13.3

PH1

Advertising