Wiring the installation backplane

Wiring
Disconnect internal PE connection

5

l

50

EDK94ZPP0364 DE/EN/FR/ES/IT 2.1

5.3

Wiring

5.3.1

Disconnect internal PE connection

If power supply (and regenerative) modules are used in drive systems, the
measures for IT systems must be strictly observed for all interconnected devices
and irrespective of the mains type (TN, TT or IT). The measures are described in
the Mounting Instructions of the devices under the keyword "IT system".
The measures provide for the following:

ƒ

Power supply modules: compliance with EMC category C2

ƒ

Regenerative power supply modules: the protection of internal capacitors

The following describes the measures for the power supply (and regenerative)
module.

IT system

1

2

SSP94IT001

Fig. 5−3

Plugging the IT insulating cap onto the earthing jumper

Proceed as follows to disconnect the internal connection between the filters
and PE:
1. Remove IT insulating cap from the parking position

 in the installation

backplane.

For this apply a screwdriver on the right or left and lever off the
insulating cap.

Optionally the insulating cap can be carefully removed using an
appropriate pliers.

2. Attach IT insulating cap to the earthing jumper

‚ until it clicks into place.