4 technical data, General data, Technical data – Lenze E82ZAFIC001 User Manual
Page 39
Technical data
General data
4
EDK82ZAFIC−001 DE/EN/FR 5.0
39
l
H1_Daten−Komm_Daten_E82ZAFICxxx
4
Technical data
General data
Field
Values
Order designation
E82ZAFIC001
Communication medium
RS485
Network topology
Ring (go and return line in the same cable)
Number of bus nodes
Dependent on INTERBUS master (e.g. Phoenix Contact G4 master).
For the following data, which depend on whether PCP
communication is used or not, always the smaller value applies:
l
with PCP communication: max. 62 or
l
without PCP communication: max. 256/number of PCDs
Distance between two bus
nodes
Max. 400 m
INTERBUS identification
(ID code)
l
With 1 word PCP: 227 (0xE3)
l
Without PCP: 3 (0x03)
Drive profile
DRIVECOM profile "Drive technology 20"
INTERBUS node
Slave
Baud rate
500 kbps
Process data words (PCD),
16 bits
1 ... 4 words
Parameter data words (PCP),
16 bits
0 or 1 word
PDU length
Max. 64 bytes
Supported PCP services
l
Initiate
l
Abort
l
Status
l
Identify
l
Get−0V−long
l
Read
l
Write
Communication time
l
Sum of the cycle time and the processing time in the bus nodes.
The times are independent of each other.
l
Processing time in the standard device
– Parameter data (PCP): approx. 30 ms + 20 ms tolerance
– Process data (PCD): approx. 3 ms + 2 ms tolerance