Operating conditions, Protective insulation, 4technical data – Lenze E82ZAFIC001 User Manual

Page 40

Advertising
background image

4

Technical data

Operating conditions

EDK82ZAFIC−001 DE/EN/FR 5.0

40

l

−H2−Schutzisolierung

Operating conditions

Ambient conditions

Climate

Storage

IEC/EN 60721−3−1

1K3 (−25 to +60 °C)

Transport

IEC/EN 60721−3−2

2K3 (−25 to +70 °C)

Operation

Corresponding to the data of the Lenze standard device used (see
documentation of the standard device).

Pollution

EN 61800−5−1

Degree of pollution 2

Degree of protection

IP20 (protection against accidental contact according to NEMA 250 type 1)

Protective insulation

Insulation between incoming bus and ...

Type of insulation (acc. to EN 61800−5−1)

l

8200 vector/motec power section

Reinforced insulation

l

Reference earth / PE

Functional insulation

l

Terminal X3.1/59

Functional insulation

l

Terminal X3.3/20

Functional insulation

l

Terminal X3.3/28

Functional insulation

Insulation between incoming bus and ...

Type of insulation (acc. to EN 61800−5−1)

Outgoing bus

Functional insulation

Insulation between outgoing bus and ...

Type of insulation (acc. to EN 61800−5−1)

l

8200 vector/motec power section

Reinforced insulation

l

Reference earth / PE

Functional insulation

l

Terminal X3.1/59

No electrical isolation

l

Terminal X3.3/20

No electrical isolation

l

Terminal X3.3/28

Functional insulation