Assignment of the terminals, Electrical installation – Lenze E82ZAFIC001 User Manual

Page 49

Advertising
background image

Electrical installation

Assignment of the terminals

6

EDK82ZAFIC−001 DE/EN/FR 5.0

49

l

H2_BelegungAnschlKlemmen−INS_Klembesch

Assignment of the terminals

Terminal
X3.1/

Designation

Function / level

59

External voltage supply of the function module

l

U = 24 V DC (21.6 V − 0% ... 26.4 V + 0 %)

l

Current consumption for 24 V DC: I = 90 mA

If the supply voltage is looped through to other bus nodes via
terminal 59, the current flowing must not exceed 3 A.

7

GND1

Reference potential for terminal X3.3/20

Terminal
X3.2/

Designation

Function / level

7

GND1

Reference potential for terminal X3.3/20

39

GND2

Reference potential for controller inhibit (CINH) on terminal X3.3/28

Terminal
X3.3/

Designation

Function / level

A

/DO1

RS485 data line (incoming)

B

DO1

C

/DI1

D

DI1

E

GND3

Reference potential for incoming data line

F

/DO2

RS485 data line (outgoing)

G

DO2

H

/DI2

J

DI2

K

GND1

Reference potential for outgoing data line

+

Additional HF shield termination

28

CINH

Controller inhibit

l

Input resistance: 3.3 k

W

l

Start = HIGH (+12 ... +30 V DC)

l

Stop = LOW (0 ... +3 V DC)

20

DC voltage source for internal supply of controller inhibit (CINH)

l

+20 V DC (reference: GND1)

l

I

max

= 10 mA