Defining the user data length, Commissioning, 1on 2 3 4 – Lenze E82ZAFIC001 User Manual
Page 55
![background image](/manuals/565911/55/background.png)
Commissioning
Defining the user data length
EDK82ZAFIC−001 DE/EN/FR 5.0
55
l
H2_NutzdatenlaengeFestlegen−nutzdatenlaenge
Defining the user data length
The number of process data words (PCD) and parameter data words (PCP) can be set via
code C1515 or via the DIP switches S2 ... S4.
)
Note!
ƒ
Sum of all data words (PZD + PCP): max. 4 words
ƒ
Switch off the voltage supply of the function module and the controller
and then on again to activate the changed settings.
Settings via DIP switches S2 ... S4
ON
OFF
1
ON
2 3 4
E82ZAFI009
ƒ If one of the DIP switches S2 ... S4 is set to OFF, the configurations resulting from all
switch positions are active at switch−on.
ƒ If the switch positions are invalid, the Lenze setting is activated:
– DIP switches S2 ... S4 = OFF (2 PCD words + 1 PCP word)
ƒ Code C1525 displays the current settings of the DIP switches S2 ... S4.
DIP switch
Value
Number of process
data words (PCD)
Number of parameter
data words (PCP)
ID code
S2
S3
S4
OFF
OFF
OFF
0
2
1
227
ON
OFF
OFF
1
3
1
227
OFF
OFF
ON
4
2
0
3
ON
OFF
ON
5
4
0
3
ON
ON
ON
Code C1515 active.