3 ethernet connection, Ethernet connection, Installation – Lenze 931K User Manual

Page 14

Advertising
background image

Installation

Electrical installation
Ethernet connection

5

l

14

KHB 13.0005−EN 1.0

5.1.3

Ethernet connection

For connection to the EtherCAT bus system a commercially available 4−pole standard
Ethernet cable is suitable.

Pin assignment

M12 socket

Pin

Signal

1

2

3

4

1

Tx +

2

Rx +

3

Tx −

931K_001

4

Rx−

Ethernet cable specifications

)

Note!

Only use cables complying with the below specifications.

Specification of the Ethernet cable

Ethernet standard

Standard Ethernet (in accordance with IEEE 802.3), 100Base−TX (Fast
Ethernet)

Cable type

S/FTP (Screened Foiled Twisted Pair, ISO/IEC 11801 or EN 50173), CAT 5e

Damping

23.2 dB (at 100 MHz and per 100 m)

Crosstalk damping

24 dB (at 100 MHz and per 100 m)

Return loss

10 dB (per 100 m)

Surge impedance

100

W

Design of the Ethernet cable

E94YCEP016

Fig. 5−3

Design of the Ethernet cable (S/FTP, CAT 5e)

A

Cable insulation

B

Braid

C

Foil shielding of the core pairs

TP1 ... TP4

Twisted core pairs 1 ... 4

Advertising