3electrical installation – Lenze E82ZAFVC010 User Manual

Page 46

Advertising
background image

3

Electrical installation

Cable specification

EDK82ZAFVC010 DE/EN/FR 2.0

46

l

H1E_INST−Merker_hidden ueb−rate

Features of the Thin" cable according to DeviceNet specifications

General features

Configuration

Two shielded symmetrical cables with a common axis and drain wire in
the centre

Total shielding

65% coverage
AWG 36 or min. 0.12 mm tinned braid (individually tinned)

Drain wire

Copper 22 min.; min. 19 cores (individually tinned)

Outer diameter

6.096 mm (min.) to 7.112 mm (max.)

Roundness

Radius deviation must be within 20% of 0.5 outer diameter

Jacket marking

Vendor name & part no. and additional markings

Spec. DC resistor (braid, tape, drain)

10.5 Ohm/1000 m (nominal at 20°C)

Certifications (U.S. and Canada)

NEC (UL), CL2 (min.)

Bend radius

20 x diameter (installation) / 7 x diameter (fixed)

Ambient operating temperature

−20°C to +70°C at 1.5 Ampere; derate current linearly to zero at 80°C

Storage temperature

−40°C to +85°C

Pull tension

289.23 N

max

Features of the data line

Insulation diameter

1.96 mm (nominal)

Conductor pair

Copper 24 min.; min. 19 cores (individually tinned)

Colours

Light−blue, white

Pair twist / m

Approx. 16

Tape shield over conductor pair

1000/1000, Al/Mylar, Al side out, w−shorting fold (pull−on applied)

Impedance

120 Ohm +/− 10% (at 1 MHz)

Propagation delay

4.46 ns/m (max.)

Capacitance between conductors

39.37 pF / m at 1 kHz (nominal)

Capacitance between a condcutor and the
conductor connected to the shield

78.74 pF / m at 1 kHz (nominal)

Capacitive unbalance

3.94 pF/1000 m at 1 kHz (max.)

Spec. DC resistor at 20°C

91.86 Ohm/1000 m (max.)

Attenuation

0.95 dB/100 m at 125 kHz (max.)
1.64 dB/100 m at 500 kHz (max.)
2.30 dB/100 m at 1.00MHz (max.)

Features of the voltage line

Conductor pair

Copper 22 min.; min. 19 cores (individually tinned)

Insulation diameter

1.4 mm (nominal)

Colours

Red, black