Status display, Commissioning – Lenze E82ZAFVC010 User Manual
Page 63
![background image](/manuals/565930/63/background.png)
Commissioning
Status display
EDK82ZAFVC010 DE/EN/FR 2.0
63
l
inbetrieb−statusanzeige AFV0xx
Status display
E82ZAFD101A*
Pos
Status display
Explanation
1
Connection status to basic device (LED, green / red)
OFF
Function module is not supplied with voltage,
external voltage supply is switched off
GREEN
BLINKING
Function module is supplied with voltage but not
connected to the controller.
Reason:
Basic device is
l
switched off
l
is being initialised
l
not available
Constantly ON
Function module is supplied with voltage and is
connected to the basic device
RED
BLINKING
Internal error, Lenze setting has been loaded
Constantly ON
Internal error of the function module
2
Connection status to bus (LED, green / red)
OFF
l
No connection with the master.
l
Function module is not supplied with voltage.
GREEN
BLINKING
Dup_Mac_ID" test phase. Not yet connected to master
(scanner).
Constantly ON
DeviceNet connection completed.
RED
BLINKING
No communication because time limit has been
exceeded
Constantly ON
Critical bus error