Electrical installation
Bus cable length
EDK82ZAFVC010 DE/EN/FR 2.0
55
l
H1E_INST−Merker_hidden ueb−rate
Bus cable length
Max. possible bus cable length
The following bus cable lengths are possible in dependence on the baud rate and the cable
used:
Baud rate [kbit/s]
Thin Cable
Thick Cable
125
100 m
500 m
250
250 m
500
100 m
When using both, Thick" and Thin" cables, the maximum cable lengths are to be selected
according to the baud rate:
Baud rate [kbit/s]
Bus cable length
125
L
max
= 500 m
= L
thick
+ 5 L
thin
250
L
max
= 250 m
= L
thick
+ 2.5 L
thin
500
L
max
= 100 m
= L
thick
+ L
thin