Function code

21

This functian allows

tor a comparison between the momentary

rotational

field trequency and a programmed trequency.

lt

the two

trequencies

are

ideritical,

the output „SAR“ is

activated tor at

least

100

insec.

The compared treguency is set in Hz.

(Factory setting is

50 Hz).

Function code 22

The opto-coupler output

T‘SST“

Is activated lt the rotational

field

freguency duririg the deceleration phase is smaller than or

equal to

the programmed frequency (0 to

3 Hz). The output is

active tor

~t

least

100 msec.

The compared freguency is set accordlng to the

tollowing table.

Data code

Inverter autput
treguency

[Hz]

Function code 23

Function code 23

determines the motor‘s mode at

operation in the

deceleration phase.

Data code

00

:

lt the rotational

tield trequency has

reduced

to

<

2 Hz,

the motor idles.

01

This data code must be selected,

it

the

inverter

is to be operated with the braking

chopper.

~

lt

the

ratational

tield

trequency

has reduced

tO

<

2Hz, the motor

is braked

down to standstill

~~iith

DC

injectian current.