Due to the construction, self−ventilated standard motors are exposed to an
increased heat generation in the lower speed range compared to forced
ventilated motors.

J

Warnings!

For complying with the UL 508C standard, you have to set the
speed−dependent evaluation of the permissible torque via code
C0129/x.

Parameter setting
The following codes can be set for I

2

x t monitoring:

Code

Meaning

Value range

Lenze setting

C0066

Display of the I

2

x t load of the motor

0 ... 250 %

C0120

Threshold: Triggering of error "OC6"

0 ... 120 %

0 %

C0127

Threshold: Triggering of error "OC8"

0 ... 120 %

0 %

C0128

Thermal motor time constant

0.1 ... 50.0 min

5.0 min

C0606

Response to error "OC8"

TRIP, warning, off

Warning

C0129/1

S1 torque characteristic I

1

/I

rated

10 ... 200 %

100 %

C0129/2

S1 torque characteristics n

2

/n

rated

10 ... 200 %

40 %