Electrical installation

Power terminals

5

l

96

EDKCSEX064 DE/EN/FR 6.0

5.2

Power terminals

ECSXA080

Fig. 5−1

Plug connectors for power terminals

{

Danger!

Dangerous voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event
of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor

diameter

³ 10 mm

2

or PE conductor must be connected twice)