5 loading a parameter set, Loading a parameter set, Parameter setting – Lenze EVF9383−EV User Manual

Page 19: Danger

Advertising
background image

Parameter setting

Parameter setting with the XT EMZ9371BC keypad

Loading a parameter set

3

l

19

EDKVF93−05 EN 2.0

3.1.5

Loading a parameter set

The keypad serves to load a saved parameter set into the main memory when the controller
is inhibited. After the controller is enabled, it operates with the new parameters.

}

Danger!

ƒ

When a new parameter set is loaded, the controller is reinitialised and acts
as if it had been connected to the mains:
– System configurations and terminal assignments can be changed. Make

sure that your wiring and drive configuration comply with the settings of
the parameter set.

ƒ

Only use terminal X5/28 as source for the controller inhibit! Otherwise the
drive may start in an uncontrolled way when switching over to another
parameter set.

)

Note!

ƒ

After switching on the supply voltage, the controller always loads parameter
set 1 into the main memory.

ƒ

It is also possible to load other parameter sets into the main memory via the
digital inputs or bus commands.

Step

Key
sequence

Action

1.

Inhibit controller

Terminal X5/28 = LOW

2.

Load the saved parameter set into the
main memory

A

z y Z Y

Select the code C0002 "PAR LOAD" in the menu
"Load/Store"

B

V

Change to the parameter level
The active parameter set is displayed, e. g. display "0"
and "Load Default"
If you want to restore the delivery status, proceed with
D

Select the parameter set to be
loaded

C

z

Load parameter set 1:
ð Set "1" "Load PS1"
Load parameter set 2:
ð Set "2" "Load PS2"
Load parameter set 3:
ð Set "3" "Load PS3"
Load parameter set 4:
ð Set "4" "Load PS4"

D

T V

"RDY" goes off. The parameter set is loaded completely
into the main memory if "RDY" is displayed again.

3.

Change to the code level

A

V

Display of the operating level

B

V

Display of C0002 "PAR LOAD"

4.

Enable controller

Terminal X5/28 = HIGH
The drive is running with the settings of the loaded
parameter set

Advertising