Key for overview, Connections and interfaces, Status displays – Lenze EVF9383−EV User Manual

Page 3

Advertising
background image

Key for overview

Position

Description

0

9300 vector frequency inverter − master

1

9300 vector frequency inverter − slave

Connections and interfaces

Position

Description

L1, L2, L3, PE Mains connection

+UG, −UG

DC supply (only for the variants V210, V240, V270, V300)

BR1, BR2

Connection of brake resistor (only for the variants V210, V240, V270, V300)

U, V, W, PE

Motor connection

X1

AIF interface (automation interface)

slot for communication module (e.g. keypad XT EMZ9371BC)

X3

Jumper for setting the analog input signal at X6/1, X6/2

X4

Terminal strip for connection of system bus (CAN)

X5

Terminal strips for connection of digital inputs and outputs

X6

Terminal strips for connection of analog inputs and outputs

X8

Sub−D connector (male) for connection of incremental encoder with TTL level or sin/cos encoder and KTY ther-
mal sensor of the motor

X9

Sub−D connector (male) for connection of digital frequency input signal

X10

Sub−D connector (female) for connection of digital frequency output signal

X11

Terminal strip for connection of relay output K

SR

for "safe standstill"

Status displays

Position

LED red

LED green

Operating status



Off

On

Controller is enabled

On

On

Mains is switched on and automatic start is inhibited

Off

Blinking slowly

Controller is inhibited

Off

On

Motor data identification is active

Blinking quickly

Off

Undervoltage or overvoltage

Blinking slowly

Off

Active fault

0Fig. 0Tab. 0