Troubleshooting and fault elimination

System error messages

General error messages

4

l

35

EDKVF93−05 EN 2.0

4.5

System error messages

4.5.1

General error messages

)

Note!

If you use GDC or a fieldbus module to retrieve the fault (C0168/x), the error
message will be represented by an error number.

Display Error number

x = 0: TRIP
x = 1: Message
x = 2: Warning

Error

Cause

Remedy

−−−

−−−

No fault

CCr

x071

System fault

Processor is overloaded or there is a
fault in the program processing

Reduce processor load. Remove function
blocks that are not needed from the
processing table

Strong interference on control cables

Shield control cables

Ground or earth loops in the wiring

Check wiring

CE0

x061

Communication
error

Fault during transmission of control
commands via automation interface X1

Plug in automation module firmly, bolt
down, if necessary

CE1

x062

Communication
error at the process
data input object
CAN−IN1

CAN−IN1 object receives faulty data, or
communication is interrupted

l

Check cable at X4

l

Check sender

l

Increase monitoring time under
C0357/1 if necessary

CE2

x063

Communication
error at the process
data input object
CAN−IN2

CAN−IN2 object receives faulty data, or
communication is interrupted

l

Check cable at X4

l

Check sender

l

Increase monitoring time under
C0357/2 if necessary

CE3

x064

Communication
error at the process
data input object
CAN−IN3

CAN−IN3 object receives faulty data, or
communication is interrupted

l

Check cable at X4

l

Check sender

l

Increase monitoring time under
C0357/3 if necessary

CE4

x065

BUS−OFF state

Controller has received too many
incorrect telegrams via system bus X4,
and has disconnected from the bus

l

Check wiring

l

Check bus termination (if any)

l

Check shield contact of the cables

l

Check PE connection

l

Check bus load

l

Reduce baud rate (observe cable
length)

EEr

x091

External fault
(TRIP−Set)

A digital input assigned with TRIP−set
function has been activated (in the most
basic configurations the input X5/E4 is
LOW−active and linked with the TRIP−set
function)

l

Check external encoder

l

Check signal at the digital input
X5/E4:
– Either connect HIGH level or
– Change polarity in C0114 to

HIGH−active. CAUTION! When
changing to HIGH level, the
wire−break protection gets lost.

The two terminal strips at X5 are
reversed

Check the position of the terminal
strips:

l

If you look at the connection unit in
reading direction, the left terminal
strip X5 must be connected with the
input signals and the right terminal
strip X5 must be connected with the
output signals.

H05

x105

Internal fault

Contact Lenze

H07

x107

Wrong power
stage

During initialisation of the controller, a
wrong power stage was detected

Contact Lenze