Troubleshooting and fault elimination

Fault elimination

Controller in clamp operation

4

l

33

EDKVF93−05 EN 2.0

If the DC−bus voltage (U

DC

) exceeds the switch−off threshold OU, pulse inhibit will be set.

At the same time, an internal timer for a delay time (C0912) will be started.

Pulse inhibit will be reset, if the voltage falls below the switch−on threshold OU and the
delay time has elapsed.

Thresholds for DC−bus overvoltage (OU)

Types EVF93xx−EVV210, EVF93xx−EVV240, EVF93xx−EVV270 and EVF93xx−EVV300

Mains voltage range

C0173

Switch−off threshold OU

Switch−on threshold OU

< 400 V

Operation with or without
brake transistor

0

770 V

755 V

400 V

Operation with or without
brake transistor

1

*

770 V

755 V

460 V

Operation with or without
brake transistor

2

770 V

755 V

480 V

Brake transistor

3

770 V

755 V

480 V

Brake transistor

4

800 V

785 V

500 V

Operation with or without
brake transistor

5

900 V

885 V

*

Lenze setting

Types EVF93xx−EV, EVF93xx−EVV060 and EVF93xx−EVV110

Mains voltage range

C0173

Switch−off threshold OU

Switch−on threshold OU

400 V

Operation with or without
brake transistor

Read only

700 V

685 V

Codes for parameter setting

Code

Possible settings

IMPORTANT

No.

Name

Lenze

Selection

C0912

OV delay time

à

{1 ms}

− Delay time of the pulse enable after

an OU message

à

Depending on C0082, C0086,
C0087, C0088, C0089, C0090,
C0091, C0092
A change of one of the codes
resets C0912 to the time of the
selected motor

l

The time is derived from the
double rotor time constant