2 controller in clamp operation, Controller in clamp operation, Troubleshooting and fault elimination – Lenze EVF9383−EV User Manual

Page 32

Advertising
background image

Troubleshooting and fault elimination

Fault elimination
Controller in clamp operation

4

l

32

EDKVF93−05 EN 2.0

4.4.2

Controller in clamp operation

The clamp operation is a permissible operating mode. But since, however, pulse inhibit is
set again and again, the controller cannot provide the optimum power.

If the output power is optimal, the output current mainly is right below the clamp
threshold.

9300vec110

Fig. 4−1

Output current when starting a motor with high load (shown with the oscilloscope in GDC)

0

Clamp threshold

1

Output current

Function

1. When the output current reaches 2.25 × I

r

, a software clamp is activated.

2. The controller sets pulse inhibit for a short time. The motor current decreases as a

function of the inductance in the motor circuit.
– An internal counter is increased by the value one.

3. After max. 250

ms the pulse inhibit is deactivated.

4. If a software clamp reoccurs within 2 s, the internal counter is again increased by the

value one. Otherwise the counter is set to zero.
– If the counter reaches the value 4300, OC3 (TRIP) is activated.