Safety

General safety and application notes for Lenze motors

2



24

EDKCSXX0XX DE/EN/FR/ES/IT 4.0

2.2

General safety and application notes for Lenze motors

(to: Low-Voltage Directive 73/23/EEC)

General
Low-voltage machines have dangerous, live and rotating parts as well as possibly hot

surfaces. All operations serving transport, connection, commissioning and maintenance

are to be carried out by qualified, skilled personnel (observe EN 50110-1 (VDE 0105-100);

IEC 60364). Improper handling may cause severe injury to persons or damage to material

assets.
Synchronous machines induce voltages at open terminals during operation.

Application as directed
These low-voltage machines are intended for industrial and commercial installations.

They comply with the harmonized standards of the EN 60034 (VDE O53O) series. Their use

in hazardous areas is prohibited unless they are expressly intended for such use (follow

additional instructions).
Degrees of protection ≤ IP23 are only intended for outdoor use when applying special

protective measures. Air-cooled designs are rated for ambient temperatures from -15 °C

and -10 °C to +40 °C and altitudes ≤ 1000 m a.m.s.l., from -20 °C to +40 °C without brake

or with spring-operated brake, non-ventilated or with integral fan, from -15 °C to +40 °C

with permanent magnet brake and from -10 °C to +40 °C with separate fan. Check

indications on the nameplate and if they are different, observe them. The conditions on

site must correspond to all nameplate data.
Low-voltage machinesare componentsfor the installation intomachinesasdefinedinthe

Machinery Directive 98/37/EC. Commissioning is prohibited until the conformity of the

end product with this Directive has been established (follow a.o. EN 60204-1).
The integrated brakes cannot be used as safety brakes. It cannot be guaranteed that

factors which cannot be influenced, such as oil ingression because of a defective A-side

shaft seal, do not cause a torque reduction.

Transport, storage
The forwarder must be informed directly after receipt of the goods about all damages or

deficiencies; if necessary, commissioning must be stopped. Tighten screwed-in ring bolts

before transport. They are designed for the weight of the low-voltage machine, do not

apply extra loads. If necessary, use suitable and adequately dimensioned means of

transport (e.g. rope guides).
Remove the shipping braces before commissioning. Reuse them for further transports. For

storage of low-voltage machines ensure a dry, dust-free and low-vibration (v

rms

≤ 0.2

mm/s) environment (damage while being stored). Measure the insulation resistance

before commissioning. If the values are ≤ 1 kΩ per volt of rated voltage, dry the winding.