Seguridad – Lenze ECS series User Manual

Page 58

Advertising
background image

Seguridad

Peligros residuales

Instrucciones de seguridad para la instalación según U

L

o U

R

2



58

EDKCSXX0XX DE/EN/FR/ES/IT 4.0

2.3.4

Instrucciones de seguridad para la instalación según U

L

o U

R

Warnings!
General markings:

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Maximum ambient temperature 55 °C, with reduced output current.

Markings provided for the supply units:

ƒ

Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 480 V max, when protected by K5 or H Fuses

(400/480 V devices).

ƒ

Alternate - Circuit breakers (either inverse-time, instantaneous trip types or

combination motor controller type E) may be used in lieu of above fuses

when it is shown that the let-through energy (i

2

t) and peak let-through

current (I

p

) of the inverse-time current-limiting circuit breaker will be less

than that of the non-semiconductor type K5 fuses with which the drive has

been tested.

ƒ

Alternate - An inverse-time circuit breaker may be used, sized upon the

input rating of the drive, multiplied by 300 %.

Markings provided for the inverter units:

ƒ

The inverter units shall be used with supply units which are provided with

overvoltage devices or systems in accordance with UL840 2nd ed., Table 5.1.

ƒ

The devices are provided with integral overload and integral thermal

protection for the motor.

ƒ

The devices are not provided with overspeed protection.

Terminal tightening torque of lb-in (Nm)

ƒ

X 21, X 22, X 23, X 24

10.6 ... 13.3 lb-in (1.2 ... 1.5 Nm)

ƒ

X4, X6, X14

1.95 ... 2.2 lb-in (0.22 ... 0.25 Nm)

ƒ

X 25

4.4 ... 7.1 lb-in (0.5 ... 0.8 Nm)

Wiring diagram AWG

ƒ

X 21, X 22, X 23, X 24

AWG 12 ... AWG 8

ƒ

X4, X6, X14

AWG 28 ... AWG 16

ƒ

X 25

AWG 24 ... AWG 12