Appendix, Code table – Lenze 8200 motec frequency inverter 0.25kW-7.5kW User Manual
Page 241

Appendix
Code table
14−40
L
EDB82MV752 EN 5.2
Code
IMPORTANT
Possible settings
No.
Selection
Lenze
Name
C0415
v
(cont.)
Possible digital signals for C0415
^ 7−73
20
Apparent motor current < current threshold
(DCTRL1−IMOT<ILIM)
V−belt monitoring
Apparent motor current = C0054
Current threshold = C0156
Frequency threshold Q
min
= C0017
21
Apparent motor current < current threshold and
output frequency > Frequency threshold Q
min
(DCTRL1−(IMOT<ILIM)−QMIN)
22
Apparent motor current < current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT<ILIM)−RFG−I=0)
23
Motor phase failure warning (DCTRL1−LP1−WARN) Set C0597 = 2
24
Minimum output frequency reached (f
£ C0010)
(PCTRL1−NMIN)
LOW active
25
TRIP error message (DCTRL1−TRIP)
26
Motor is running (DCTRL1−RUN)
27
Motor is running / CW rotation (DCTRL1−RUN−CW)
28
Motor is running / CCW rotation
(DCTRL1−RUN−CCW)
29
Process controller input = process controller
output (PCTRL1−SET=ACT)
30
Reserved
31
Apparent motor current
>
Current threshold and
ramp function generator 1: input = output
(DCTRL1−(IMOT>ILIM)−RFG−I=0)
Overload monitoring
Apparent motor current = C0054
Current threshold = C0156
32
Digital input X3/E1
digital inputs
33
Digital input X3/E2
34
Digital input X3/E3
35
Digital input X3/E4
36 (A)
Digital input X3/E5
37 (A)
Digital input X3/E6
38
PTC input X2.2/T1, X2.2/T2
Only connect potential−free switches to
T1/T2!
T1/T2 is active ("HIGH") when the switch is
closed